Explosion-proof flexible heating low temperature HV self-regulating cable GTG-KABEL1-65 (RETO-CORD/S/R65-S-LD)

+
x
<
>
Explosion-proof flexible heating low temperature HV self-regulating cable GTG-KABEL1-65 (RETO-CORD/S/R65-S-LD)PURPOSE AND SCOPE OF APPLICATIONВзрывозащищенный гибкий греющий низкотемпературный кабель высокой мощности с саморегулировкой температуры ГТГ-КАБЕЛЬ1-65

Explosion-proof flexible heating self-regulating cable is intended for heating and maintaining of process temperature of automation facilities, reservoirs, pipes and other facilities that require additional protection against freezing and icing.

Heating element material shrinks at low temperatures creating lots of carbon current-conducting paths and reducing electrical resistance. When electric current flows via heating element, a thermal energy output occurs.

Heating element material expands in warmer sections of the explosion-proof heating cable, reducing number of current-conducting paths. Electrical resistance of heating element material increases, resulting in a significant thermal energy output reduction.

Expansion of material of heating element in hot spots of the heating cable almost entirely tears current-conducting paths. Along with that, electric resistance of material becomes very high, which leads to significant reduction of heat energy output.

Принцип работы Взрывозащищенные гибкие греющие кабели ГТГ-КАБЕЛЬ1

Scope of application - explosive zones of premises and outdoor installations, in accordance with the accepted explosion protection marking, the requirements of GOST IEC 60079-14-2013 and industry Safety Rules governing the use of this equipment in explosive conditions.

+
CONFORMITY TO STANDARDS IN RUSSIA
ГОСТ Р МЭК 60079-0-2011, ГОСТ 14254-96 (МЭК 529-89), ГОСТ 30852.0-2002 (МЭК 60079-0:1998), ГОСТ Р МЭК 62086-1-2003, ГОСТ 30852.8-2002 (МЭК 60079-0:1998), ТР ТС 012/2011, ТР ТС 004/2011, ГОСТ IEC 61241-1-1-2011, ГОСТ 24754-2013, Гл. 7.3 ПУЭ, Гл. 7.4 ПУЭ, ГОСТ 30852.20-2002, ГОСТ Р МЭК 60079-31-2010
+
CERTIFICATES
Маркировка взрывозащиты Marking:
1Ex e IIC T6 Gb X
Ex tb IIIC T75°C Db X
Protection:
+
TECHNICAL DATA
Ambient temperature, °С:
-60...+65
Supply voltage, V:
~230
Power, W:
10, 15, 25, 30, 50, 66
Operating position in space:
Any
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1, W5)
+
DIMENSIONS, OPTIONS, ACCESSORIES
MARKING
Non-explosion-proof version
/PROM
Cable element for heating cable end termination
/GTG-ZGK
+
OVERALL AND MOUNTING DIMENSIONS
Technical data for heating cables type GTG-KABEL1-65
Type GTG-KABEL1-65-10 GTG-KABEL1-65-15 GTG-KABEL1-65-25 GTG-KABEL1-65-30 GTG-KABEL1-65-50 GTG-KABEL1-65-66
Rated power, W/m 10 ±10% 15 ±10% 25 ±10% 30 ±10% 50 ±10% 66 ±10%
Maximum maintained temperature, °C +(70±5) +(70±5) +(70±5) +(70±5) +(70±5) +(70±5)
Maximum allowable temperature without load (1000 hours in total) +85 +85 +85 +85 +85 +85
Minimum installation temperature, °C -60 -60 -60 -60 -60 -60
Nominal cable size, mm 13,4 х 5,5 13,4 х 5,5 13,4 х 5,5 13,4 х 5,5 13,4 х 5,5 13,4 х 5,5
Maximum length of heating section at ambient temperature -20°C, m 150 150 100 100 100 100
Temperature class Т6 Т6 Т6 Т6 Т6 Т6
Cable sheath material Fluorinated ethylene propylene Fluorinated ethylene propylene Fluorinated ethylene propylene Fluorinated ethylene propylene Fluorinated ethylene propylene Fluorinated ethylene propylene
Maximum circuit length when using type "C" circuit breakers in accordance with EN 60898 at 230V
Dimensions of electrical protection installation Switch-on temperature, °C Maximum heating cable length per circuit (m) at 230V AC
GTG-KABEL1-65-10 GTG-KABEL1-65-15 GTG-KABEL1-65-25 GTG-KABEL1-65-30 GTG-KABEL1-65-50 GTG-KABEL1-65-66
16A (-20°C) 95 70 55 45 30 25
(+10°C) 95 70 55 45 30 25
25A (-20°C) 155 120 95 75 50 40
(+10°C) 155 120 95 75 50 40
32A (-20°C) 200 150 120 100 70 50
(+10°C) 200 150 120 100 70 50
40A (-20°C) 255 195 150 130 90 70
(+10°C) 255 195 150 130 90 70
+
FORMATION OF MARKING
GTG-KABEL1   Х   Х   Х   Х  – TU 28.21.13-041-72453807-2017
                  Type of device
                  Maximum maintained operating temperature t °C: 65
                  Power, W: 10, 15, 25, 30, 50, 66
                  Length in meters
                  Options, accessories and versions

Example: GTG-KABEL1-65-30-100-TU 28.21.13-041-72453807-2017

+
Diagram of dependence of linear power on temperature
Power, W/m
График зависимости линейной мощности от температуры ГТГ-КАБЕЛЬ1
Pipe temperature, °С

А – GTG-KABEL1-65-66

B – GTG-KABEL1-65-50

C – GTG-KABEL1-65-30

D – GTG-KABEL1-65-25

E – GTG-KABEL1-65-15

F – GTG-KABEL1-65-10

Устройство саморегулирующегося кабеля


Self-regulating cable structure:

1. Current-conducting stranded tin-plated copper cores.

2. Thermoresistive element.

3. Internal insulation for provision of dielectric strength, moisture tightness, protection against impact loads and abrasion, as well as protection against chemical exposure for heat-producing matrix.

4. Outer insulation.

5. Tinned copper protective braid.

6. Fluoropolymer outer protective sheath is applied in conditions of increased humidity as well as under the exposure of organic substances and solvents or other aggressive substances in common areas or in areas classified as hazardous.

+