Compact explosion-proof switching module SHGV-VA (CCA-ABT) with circuit breaker

+
x
<
>
Compact explosion-proof switching module SHGV-VA (CCA-ABT) with circuit breakerPURPOSE AND SCOPE OF APPLICATION

Compact explosion-proof switching module SHGV-VA (CCA-ABT) with circuit breaker are intended for control and protection against overloads, short circuit in electric circuit. Electromagnetic circuit breaker which has 1 to 4 poles with fixed current rate installed in SHORVA explosion-proof enclosure; internal and external earth bolts are provided. Industrial type reliable circuit breakers series Schneider Electric (trade mark Merlin Gerin) are used in the devices, other types of circuit breakers are installed upon customer‘s request. Short circuit trip curve by default, curve D upon request.

For direct entry of cables or wires into Exd enclosure of the switching module, specially developed Exd cable glands series KNV, KOV, KNVTN, KNVTV, KNVM and with encapsulation series KNVZ are used. In accordance with the mandatory requirements, characteristics are given in the certificate. This allows us not to use inlet junction box, which makes the products of "ZAVOD GORELTEX" Co. Ltd. unique compared with products of other companies.

Full production cycle starting from casting molds and to ready product is performed at the explosion-proof equipment plant “ZAVOD GORELTEX” Co. Ltd. on the territory of the Russian Federation.

IMPORTANT TO KNOW: Some "garage" manufacturers from different countries assemble switching modules (Exd type of protection) with direct insertion, installing ordinary Exd cable glands (no data in certificates). These products are EXPLOSIVE, since these glands do not ensure flame protection in case of aging of sealing.

Scope of application - hazardous indoor and outdoor areas in accordance with explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996) and areas hazardous with combustible dust ignition, as per GOST IEC 61241-3-2011, dangerous production facilities of I, II, III, IV hazard classes under supervision of Rostekhnadzor and national supervisory bodies of the CU and the CIS countries

+
CONFORMITY TO STANDARDS IN RUSSIA
ГОСТ Р МЭК 60079-0-2011, ГОСТ 30852.0-2002 (МЭК 60079-0:1998), ГОСТ 30852.1-2002 (МЭК 60079-1:1998), ГОСТ 30852.20-2002, ТР ТС 012/2011, ГОСТ IEC 61241-1-1-2011, ГОСТ 14254-96 (МЭК 529-89), Гл. 7.3 ПУЭ, Гл. 7.4 ПУЭ, РД 5.2-093-2004, ГОСТ Р МЭК 60079-31-2010
+
CERTIFICATES
Маркировка взрывозащиты Marking:
1Ex db IIC T6...T5 Gb
Ex tb IIIC T85°С ...T100°С Db
Mining equipment marking:
РВ Ex d I Mb (по согласованию)
Protection:
+
TECHNICAL DATA
Ambient temperature, °С:
-60...+40/+55
-20...+40/+55 (for minimg equipment)
Maximum voltage, V:
1000/250
Maximum current, A:
160
Coating:
Antistatic polymer-epoxy coating, frictionally intrinsically safe, resistant to operating environment and ionizing radiation Цвет RAL 7035
Enclosure material:
Modified corrosion-resistant aluminum-silicon alloy, resistant to salt spray and other chemical substances including hydrogen sulfide and hydrochloric acid vapors, saline and acidic mine waters, frictionally intrinsically safe
Electric shock hazard protection class:
I
Mass, kg:
4
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3,T5, MU1, MU2, MU3, MU4, W2.1, W5)
+
DIMENSIONS, OPTIONS, ACCESSORIES
MARKING
Heating for automation
/OBOGREV
Internal thermal insulation
/TEPLOIZOLJCIJA
External surface coating as per customer’s specification
/RAL (___)
Acceptance by customer
/PRIEMKA
Earthquake-resistant version
/MSK-64
Version for tropics with protection against bugs
/TERMITY
Drain plug for condensate removal
/DKUV
Anti-condensation coating
/AP
Additional contacts (state contact, signal contact)
/DK
Motor drive for remote control
/PDU
+
OVERALL AND MOUNTING DIMENSIONS

For rated current up to 63А**

Модуль коммутации взрывозащищенный
ШГВА-ВА с автоматическим выключателем

 

For rated current from 80А to 125А**

Модуль коммутации взрывозащищенный
ШГВА-ВА с автоматическим выключателем

** For mining explosion-proof version, miming input terminal boxes with Exd type of protection are used.
Design parameters for 160 A are provided upon request

Installation of input box with terminal adaptors is required if cable cores’ cross section is more than:
- 25 mm2 for modular circuit breakers 0,5 – 25А;
- 35 mm2 for modular circuit breakers 32 – 63А;
- 50 mm2 for modular circuit breakers 80 – 125А.

                                  Standard circuit breakers SHGVA-VA
Marking for order Description
SHGVA-VA -1-6 Circuit breaker 1-pole  I=6 A
SHGVA-VA -1-10 Circuit breaker 1-pole  I=10 A
SHGVA-VA -1-16 Circuit breaker 1-pole  I=16 A
SHGVA-VA -1-20 Circuit breaker 1-pole  I=20 A
SHGVA-VA -1-25 Circuit breaker 1-pole  I=25 A
SHGVA-VA -1-32 Circuit breaker 1-pole  I=32 A
SHGVA-VA -1-40 Circuit breaker 1-pole I=40 A
SHGVA-VA -1-63 Circuit breaker 1-pole  I=63 A
SHGVA-VA -1-80 Circuit breaker 1-pole  I=80 A
SHGVA-VA -1-100 Circuit breaker 1-pole  I=100 A
SHGVA-VA -1-125 Circuit breaker 1-pole  I=125 A
SHGVA-VA -1-160 Circuit breaker 1-pole  I=160 A
SHGVA-VA -2-6 Circuit breaker 2-pole  I=6 A
SHGVA-VA -2-10 Circuit breaker 2-pole  I=10 A
SHGVA-VA -2-16 Circuit breaker 2-pole  I=16 A
SHGVA-VA -2-20 Circuit breaker 2-pole  I=20 A
SHGVA-VA -2-25 Circuit breaker 2-pole  I=25 A
SHGVA-VA -2-32 Circuit breaker 2-pole  I=32 A
SHGVA-VA -2-40 Circuit breaker 2-pole  I=40 A
SHGVA-VA -2-63 Circuit breaker 2-pole  I=63 A
SHGVA-VA -2-80 Circuit breaker 2-pole  I=80 A
SHGVA-VA -2-100 Circuit breaker 2-pole  I=100 A
SHGVA-VA -2-125 Circuit breaker 2-pole  I=125 A
SHGVA-VA -2-160 Circuit breaker 2-pole  I=160 A
SHGVA-VA -3-6 Circuit breaker 3-pole  I=6 A
SHGVA-VA -3-10 Circuit breaker 3-pole I=10 A
SHGVA-VA -3-16 Circuit breaker 3-pole I=16 A
SHGVA-VA -3-20 Circuit breaker 3-pole I=20 A
SHGVA-VA -3-25 Circuit breaker 3-pole I=25 A
SHGVA-VA -3-32 Circuit breaker 3-pole I=32 A
SHGVA-VA -3-40 Circuit breaker 3-pole I=40 A
SHGVA-VA -3-63 Circuit breaker 3-pole I=63 A
SHGVA-VA -3-80 Circuit breaker 3-pole I=80 A
SHGVA-VA -3-100 Circuit breaker 3-pole I=100 A
SHGVA-VA -3-125 Circuit breaker 3-pole I=125 A
SHGVA-VA -3-160 Circuit breaker 3-pole I=160 A
SHGVA-VA -4-6 Circuit breaker 4-pole I=6 A
SHGVA-VA -4-10 Circuit breaker 4-pole I=10 A
SHGVA-VA -4-16 Circuit breaker 4-pole I=16 A
SHGVA-VA -4-20 Circuit breaker 4-pole I=20 A
SHGVA-VA -4-25 Circuit breaker 4-pole I=25 A
SHGVA-VA -4-32 Circuit breaker 4-pole I=32 A
SHGVA-VA -4-40 Circuit breaker 4-pole I=40 A
SHGVA-VA -4-63 Circuit breaker 4-pole I=63 A
SHGVA-VA -4-80 Circuit breaker 4-pole I=80 A
SHGVA-VA -4-100 Circuit breaker 4-pole I=100 A
SHGVA-VA -4-125 Circuit breaker 4-pole I=125 A
SHGVA-VA -4-160 Circuit breaker 4-pole I=160 A
+
FORMATION OF MARKING
SHGV-VA  -  X  -  Х  -  -X Х  /  Х  – TU 3400-005-72453807-07











                    Product name
                    Number of poles of CB
                    Rated current
                    Quantity of cable glands
                    Type of cable glands
                    Options, accessories and versions

Example of order: SHGV-VA-2-16-2KNV2 -TU 3400-005-72453807-07
SHGV-VA device, complete with:
- 2-pole circuit breaker 16А with operating handle
- 2 cable glands KNV2 for non-armored cable

+