Explosion-proof support brackets for thermal insulation ОКТ3 (FRAME-P1CORD)

+
+
x
<
>
Explosion-proof support brackets for thermal insulation ОКТ3 (FRAME-P1CORD)PURPOSE AND SCOPE OF APPLICATION

OKT3 support brackets are used to insert a heating cable under the layer of thermal insulation. They make it possible to insert a heating cable under the layer of thermal insulation, simplifying the mounting and preventing damage of heating cable. Explosion-proof support brackets are designed in such a way that they are easily fastened to circular cross-section conduits.

Increased diameter of the support bracket as well as use of fiberglass-reinforced impact-resistant antistatic polyester with addition of graphite ensure resistance to impact loads.

Explosion-proof support brackets are installed on the conduit by means of two metal fastening clamps.

OKT3 explosion-proof support brackets are used as a part of finished explosion-proof boxes for connection of power supply to the heating accessories under the thermal insulation.

Scope of application – outdoor and indoor hazardous areas as per explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996), areas with presence of combustible dust, as per GOST IEC 61241-3-2011, dangerous production facilities of I, II, III, IV hazard class supervised by Rostechnadzor of the RF and national technical supervision bodies of the Customs Union and CIS countries.

+
CONFORMITY TO STANDARDS IN RUSSIA
ГОСТ 14254-96 (МЭК 529-89), ГОСТ 30852.0-2002 (МЭК 60079-0:1998), ГОСТ 30852.1-2002 (МЭК 60079-1:1998), ГОСТ 30852.8-2002 (МЭК 60079-0:1998), ГОСТ 30852.10-2002 (МЭК 60079-11:1999), ГОСТ IEC 61241-1-1-2011, Гл. 7.3 ПУЭ, Гл. 7.4 ПУЭ, ТР ТС 012/2011, ГОСТ 24754-2013, ГОСТ 30852.20-2002
+
CERTIFICATES
Маркировка взрывозащиты Marking:
1Ex e IIС Gb X*
2Ex nR IIС Gc X*
Ex tb IIIC Db X*
Ex e IIС Gb U
Ex nR IIС Gc U
Ex tb IIIC Db U
*условия указаны в руководстве по эксплуатации *conditions are specified in the operating instructions
+
TECHNICAL DATA
Ambient temperature, °С:
-40... +135
-20... +135 (for РН1, РН2)
Maximum voltage, V:
800
Maximum current, A:
175
Thread:
M48х2 GOST 24705
Size of connected heating cable, mm:
up to 13,7
Material:
Fiberglass-reinforced impact-resistant antistatic polyester with addition of graphite, chemically resistant to operating environments and ultraviolet radiation.
Fixation on pipe:
1 fastening clamp on pipe
Mass, kg:
0,21
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1, W5)
+
DIMENSIONS, OPTIONS, ACCESSORIES
MARKING
Set of metal fastening clamps (2 pcs.)
/2*A45
+
OVERALL AND MOUNTING DIMENSIONS
Explosion-proof support brackets for thermal insulation ОКТ3 УExplosion-proof support brackets for thermal insulation ОКТ3


Minimum dimensions of heating cables, mm Maximum dimensions of heating cables, mm
a b A B
3 11 6,2 13,7
+
FORMATION OF MARKING
ОКТ3 Х  – TU 3400-007-72453807-07
      Options, accessories and versions

Example: ОКТ3–TU 3400-007-72453807-07

+